03/22/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL


FROM: PDSD Zoning Review

PROJECT:
T22CM00751
492 S Convent Ave – HO-3
SFR Addition & Remodel (2nd Review)

TRANSMITTAL: March 22, 2022
COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8).

This site is located in the HO-3 zone (UDC 4.7.15).

1. Until the Historic Review has been completed and approved Zoning cannot approve the building plans. The addition/remodel requires Historic review prior to approval of this building permit.

Per UDC TABLE 6.3-3.A: DIMENSIONAL STANDARDS FOR THE O-1, O-2, & O-3 ZONES, O-3 Zone the required interior perimeter yard setback is 10’ or 3/4 (H), (H) = Height of the proposed exterior building wall, as measured from design grade to the highest point of the wall.
2. Based on a wall height of 14’-7” the required perimeter yard setback from the
proposed addition to the south property line is 11’-0”, proposed setback is 0’-0”. Historic Review can waive perimeter yard setbacks.

Historic application/requirements can be found at: https://www.tucsonaz.gov/files/pdsd/Preservation/HPZ_Review_Application_Package_2020.pdf, and is a separate submittal from the building plans submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using Submission Type “Historic Review”.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.