Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Provide a complete electrical line diagram showing the new service(s) and all associated electrical equipment address(s), suite or apartment numbers also. Include; (a) Site plan showing the location of the service on the building (only if not the same location as the existing). (b) AIC rating of the electrical equipment and available fault current per TEP. (c) Show all conduit, conductor sizes and types, riser and feeders. (e) If using Panels or load centers as the service main disconnecting means and also servicing building loads, provide a complete panel schedule. If the load is increasing, provide load calculations. If not, include a note stating “NO CHANGE IN LOAD” on the plan. (f) Show grounding.

If the subsequent submittal Design and Calculations are not up to Engineering design standards, the applicant may need to obtain the services of an Electrical Engineer registered in the State of Arizona



Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.