Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM00211
Parcel: 10704002C

Address:
1401 W GLENN ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00211
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00211
GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Denied
E1.1: No electrical issues
E2.1: Need to provide conductor and conduit sizes information or table for all feeders that need to be larger than #12 AWG. This information can be included in the Keynotes, in the panel schedules, or on the homerun tags.
E3.1: Need to provide interior lighting Comcheck. Response indicates a Comcheck was performed, but it was not in our review documents.
E4.1: Should provide Short Circuit calculations as this is a Tucson city requirement.
E5.1: No electrical issues


PLUMBING REVIEW COMMENTS:
Denied
Second Plumbing review:
1). OK
2). SAME-Add gutter & downspout sizes with calculations to plan pages A3.2 that derive from -IPC 1106.3 & 1106.6 ** Plan page A3.2 Key Note#2 shows gutters and downspouts**
3 thru 5 OK
6). SAME-Add the backflow preventer information to plan pg. P2.0 -IPC A106.3.1, 303.1, 608.1 ** Need the backflow device manufacturer name & model for the backflow at the interior storage tanks on plan page P1.0**
7 thru 8 OK


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
07/14/2022 JVINCEN1 FIRE REVIEW Approved
07/19/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM00211 - Stockett Tile & Granite
1401 W Glenn St – I-1
Building Addition (2nd Review)

TRANSMITTAL: July 19, 2022

This site is located in I-1 zone (4.7.29), General Manufacturing is an allowed use in the zone (UDC Table 4.8-5), subject to Use Specific Standards 4.9.5.C.2, .6, .7, & .8 and 4.9.13.Q.

1. Zoning as reviewed the building plans for compliance with DP21-0340 and although it appears that the building plans match the DP as required information was not provided on the DP Zoning cannot approve the building plans. Zoning will review for compliance on the next submittal.

2. If the development package sheets are to be provided in the building plan set the either need to be; stamped approve DP set, or marked for reference only.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/19/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
07/19/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov