Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM00211
Parcel: 10704002C

Address:
1401 W GLENN ST

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T22CM00211
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2022 ROBERT SHERRY WATER REVIEW Completed
02/01/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM00211 - Stockett Tile & Granite
1401 W Glenn St – I-1
Building Addition (1st Review)

TRANSMITTAL: February 1, 2022

This site is located in PAD-16 Medical Service is an allowed use in the PAD

1. Zoning as reviewed the building plans for compliance with DP21-0340 and although it appears that the building plans match the DP as required information was not provided on the DP Zoning cannot approve the building plans. Zoning will review for compliance on the next submittal.

2. If the development package sheets are to be provided in the building plan set the either need to be; stamped approve DP set, or marked for reference only.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
02/04/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00211

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Refer to Architectural Drawing A3.2 and Structural Drawing S3.1. The Architectural Drawing calls for 5' overhang and Structural Drawing calls for 3’-6” max. Verify and make revisions as needed.
2. Structural steel, components and fasteners which are exposed, are to be protected against corrosion in accordance with AISC 360 Section B.13 as indicated in IBC 2018 Section 2203.1


BUILDING REVIEW COMMENTS:
Denied
1. An occupant load calculation must be provided. Numbering the amount of employees is the incorrect method to determine the occupant load. Provide a correct occupant load in accordance with Section 1004 and Table 1004.5. Additionally, the new occupant load will require additional plumbing facilities.
2. Provide existing and demolition floor plans.
3. Provide clarification to the nature of the operations occurring in the space and how it aligns with an F-1 occupancy.
4. Provide a thorough egress plan.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. Approved/Subject to field approval.


ELECTRICAL REVIEW COMMENTS
Denied
Need to provide interior lighting Comcheck.
Need to provide conductor and conduit sizes information or table for all feeders that need to be larger than #12 AWG. Often included in panel schedule or on homerun tag.
Other comments:
Should NOT put any stamp / seal over the EOR's PE seal. Could barely discern PE's name or number. This could have caused the set to be denied.
Typically should provide Short Circuit calculations as this is a Tucson city requirement. Panels are rated above TEP short circuit value, making this a moot requirement.


PLUMBING REVIEW COMMENTS:
Denied
1).Per Plan Pg. CVR the following pages are missing. P1.2, P2.1, P3.1, P3.2...... Roof plan A2.4 & Site details A1.2. -IPC A106.3.1
2). Add gutter & downspout sizes with calculations to plan pages A3.1 & A3.2 that derive from -IPC 1106.3 & 1106.6
3). This occupancy load & type requires a service sink. -IPC 403.1
4). Plan Pg. P1.0 needs to illustrate the trench drain piping, it's not being shown connecting to any system. -IPC 301.3
5). Will the trench drain on P1.0 be required to discharge thru an oil/sand interceptor? what will be discharging to the trench drain other that water treatment discharge? plans show the fabrication floor area being sloped to the trench drain. IPC 1003.1
6). Add the backflow preventer information to plan pg. P2.0 -IPC A106.3.1, 303.1, 608.1
7). Evap water connections on Plan Pg P1.0 need backflow protection. -IPC 608.3
8). Water service on Plan page C2 undersized shows 1.5" & plan pg. P1.0 shows 2". The plan pages need to correlate. -IPC A106.3.1, 604.3
02/07/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
02/25/2022 JPEELDA1 FIRE REVIEW Reqs Change 1. An occupant load calculation must be provided. Numbering the amount of employees is the incorrect method to determine the occupant load. Provide a correct occupant load in accordance with Section 1004 and Table 1004.5. Additionally, the new occupant load will require additional plumbing facilities.
2. Provide existing and demolition floor plans.
3. Provide clarification to the nature of the operations occurring in the space and how it aligns with an F-1 occupancy.
4. Provide a thorough egress plan.
5. If new building provide notes stating new fire sprinkler system to be installed and a permit obtained from TFD

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
03/01/2022 ARUIZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change

Final Status

Task End Date Reviewer's Name Type of Review Description
03/02/2022 NGARCIA3 OUT TO CUSTOMER Completed