Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM00130
Parcel: 13704155A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00130
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change
03/09/2022 ROBERT SHERRY WATER REVIEW Completed
03/09/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00114/BLDG #1, T22CM00127/BLDG#2, T22CM00128/BLDG#3, T22CM00129/BLDG#4, T22CM00130/BLDG#5

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
1. All exposed steel to be protected from corrosion using paint or galvanized.
2. All wood members which are exposed to weather are required to be protected.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E311 ELECTRICAL PLAN - BUILDING TYPES A & B - LEVEL 1: Missing Key Note #9, may have referenced Notes# 9.
E321 ELECTRICAL PLAN - BUILDING TYPES C & C ADA LEVEL 1: Missing Key Note #9, may have referenced Notes# 9.
E331 ELECTRICAL PLAN - BUILDINGS D LEVEL 1 & 2: Missing Key Note #9, may have referenced Notes# 9.
E501 ELECTRICAL DIAGRAMS: Missing Keynotes #7 and #8 (probably lighting contactor and photocell info.


PLUMBING REVIEW COMMENTS:
Denied
Second Review:
1 thru 4 OK
5). SAME-Fire main on P100 needs proper backflow protection. Tucson Amendment -IPC 608.17.4 ( no response)
6 thru 16 OK


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/10/2022 JPEELDA1 FIRE REVIEW Approved
03/17/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
03/17/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM00114/BLDG #1, T22CM00127/BLDG #2, T22CM00128/BLDG #3, T22CM00129/BLDG #4, T22CM00130/BLDG #5,
T22CM00131/BLDG #6, T22CM00132/BLDG #7
5301 S Nogales Hy – C-2, O-3 & R-2
Multi-Family (2nd Review)

DATE: March 17, 2022

Provide a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2, O-3 & R-2 zones.

1. Zoning has reviewed the building plans for compliance with Development Package (DP) DP21-0312 and although the buildings appear to be in compliance with the DP Zoning cannot approve the building plans until the DP is approved.

2. Zoning acknowledges that a unit type schedule was provided. Please provide what type and number are provided for each different building type.


If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.