Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Plan Number: T21PRE0235
Parcel: Unknown

Review Status: Active

Review Details: PREAPPLICATION MEETING

Plan Number - T21PRE0235
Review Name: PREAPPLICATION MEETING
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2021 ELISA HAMBLIN ZONING REVIEW Completed Rezoning Pre-Submittal Transmittal

FROM: Elisa Hamblin, AICP
PDSD Zoning Review

PROJECT: Rezoning Pre-submittal meeting T21PRE0235
Address: 831 E Limberlost Dr
Parcel(s): 105-10-2560, -2670, -2660, -2570, -2580, -2590, -2600, -2610, -2620, -2630, -2640, -2650
Existing Zoning: MH-1
Proposed Zoning: R-3
Existing Use: Vacant
Proposed Use: Multifamily Development

TRANSMITTAL DATE: November 23, 2021

COMMENTS:
1. Development must comply with the Administrative Manual Section 2-06 - Development Package.
2. Proposed use and use-specific standards: Multifamily Development
3. Development standards: 36 units/acre, 70% lot coverage, 40 ft building height
4. Perimeter yard setbacks: north, east, and west = 10 ft or ¾ the wall height, whichever is greater
5. Applicable street setbacks: 20 ft or 1.5 times the wall height, as measured from property line
6. Parking requirements: See UDC Article 7.4.4 https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-5445
7. Bike parking requirements: See UDC Article 7.4.8 https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-5698
8. Landscape requirements can be discussed further with Anne Warner at Anne.Warner@tucsonaz.gov
9. Additional comments:
a. The existing development does permit multifamily development, but at a lower density and height limit.
b. A lot combination will be required prior to approval of the Development Package.
10. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions please contact me at elisa.hamblin@tucsonaz.gov.
11/23/2021 BILLIE LEE COMMENTS COMMENTS Active
11/23/2021 ANY ELECTRICAL ENGINEERING REVIEW Active
11/23/2021 ANY CONSTRUCTION ESTIMATE REVIEW Active
11/23/2021 JOHN BEALL M&C Public Hearing 4 Plan Amendment Set M&C Public Hearing Date Active
11/30/2021 MROSS2 FIRE REVIEW Approved Automatic sprinkler systems will be required

A fire alarm alarm system will be required

A fire hydrant is required within 600' of all portions of every building

Aerial apparatus access will be required for buildings over 30' in height

2 separate fire access roads are required



Michael Ross
Tucson Fire Department
520-837-7082
Michael.Ross2@tucsonaz.gov