Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM09873
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/03/2022 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Provide the civil site plan showing the installation of the water service and other on-site utilities to the building as part of the construction documents (i.e. not "for reference only"). Reference: Sections 107.2.1 and 107.2.6, IBC 2018. [Initial comment: Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water (typically directly after the water meter) for buildings that have food service facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf.] |
| 03/14/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM09873 4700 S Landing Wy – PAD-29 New Building for Commercial Recreation (2nd Review) TRANSMITTAL: March 14, 2022 This site is located in PAD-29. Commercial Recreation is a permitted use in the PAD. Provide a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. It is not clear what lot the use is proposed on. None of the building within the area indicated on the site location map or address 4700 match the 48,000 SF. Until clarified Zoning cannot approve the building plan. A change to development package DP16-044 may be required. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov |
| 03/18/2022 | SBLOOD1 | ENGINEERING | REVIEW | Approved | |
| 03/21/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | IFC 2018, Section 1015.7 Roof Access. Guards shall be provided where the roof hatch opening is located within 10 feet of a roof edge or open side of a walking surface and such edge or open side, is located more than 30 inches above the floor, roof or grade below. The guard shall be constructed as tp prevent the passage of a sphere 21 inches in diameter. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 Fire Plans Examiner |
| 04/07/2022 | CVASQUE2 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/07/2022 | CVASQUE2 | APPROVAL SHELF | Completed |
| 04/07/2022 | CVASQUE2 | OUT TO CUSTOMER | Completed |
| 04/07/2022 | CVASQUE2 | REJECT SHELF | Completed |