Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM09873
Parcel: 137055740

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL

Permit Number - T21CM09873
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2022 ROBERT SHERRY WATER REVIEW Reqs Change Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water (typically directly after the water meter) for buildings that have food service facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
01/21/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM09873
4700 S Landing Wy – PAD-29
New Building for Commercial Recreation (1st Review)

TRANSMITTAL: January 21, 2022
This site is located in PAD-29. Commercial Recreation is a permitted use in the PAD.

1. It is not clear what lot the use is proposed on. None of the building within the area indicated on the site location map or address 4700 match the 48,000 SF. Until clarified Zoning cannot approve the building plan. A change to development package DP16-044 may be required.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
01/21/2022 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
02/04/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
02/24/2022 JPEELDA1 FIRE REVIEW Reqs Change Sheet T1.0 Code Summary references the 2007 NEC Should be the 2017.
Sheet T1.0 Scope of work should note deferred submittals: fire alarm (voice evacuation system), fire sprinkler and fire sprinkler underground, kitchen fire suppression system, CO2 gas detection alarm system.
Confirm that electrical room door meets IFC 1010.1.10

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@tucsonaz.gov
520-837-7033
Sheet A1.4D shows a roof access ladder with cage. Please provide diagram of laddre cage as some OSHA compliant cages do not accommodate a fire fighter with SCBA.
02/25/2022 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Completed
02/25/2022 DBENOIT1 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/28/2022 NGARCIA3 OUT TO CUSTOMER Completed