Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM09774
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/05/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 05/05/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 05/06/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM09774 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Conditionally Approved Approval is for the Foundations only. BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Denied Fourth Plumbing Review: 1 thru 10 11). now that the plans have been compared to buildout plans, plan page 1P201C grease system can't recieve discharge from restroom fixtures. -IPC 1003.2 If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 05/11/2022 | SBLOOD1 | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/11/2022 | DBENOIT1 | APPROVAL SHELF | Completed |
| 05/11/2022 | DBENOIT1 | OUT TO CUSTOMER | Completed |
| 05/11/2022 | DBENOIT1 | REJECT SHELF | Completed |