Permit Number: T21CM09774
Parcel: 14101925B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM09774
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2022 DBENOIT1 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09774

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
Second Review:
1). Now that the storm drain stub-outs on plan pages 1P201A thru 1P201E show the GPM loads, the Keyed notes 11 refer to 4" roof conductor up, the vertical GPM max is 180gpm, several undersized. B) -Also show the outgoing horizontal 6" storm on plan Pg 1P201C being undersized, the max 1/4" slope GPM is 487 -IPC 1106.2
C)- Plan Page 1P201C shows 4" storm stub up connecting to 3" horizontal out, can't decease in direction flow. -IPC 1101.5
2). SAME-Provide the civil site utility piping plan to see that it correlates with the foundation plan water, storm, & sewer stubouts. -IPC A106.3.1 3 thru 6 OK
7). The install notes for the underground gas piping on plan 1P301C needs to comply with IFGC 404.11, 404.14,
8). The install notes for the underground gas piping on plan 1P301E needs to comply with IFGC 404.11, 404.14,
9). OK
10). Add the type of joint connection style for gas piping 4" or larger to plan page 1P301E and or 1P001 -IFGC 403.10.5 (1)
03/11/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM09774
5755 S Houghton Rd – PAD-12
Medical Service – Major (2nd Review) – DP21-0302

TRANSMITTAL: March 11, 2022
This site is located in PAD-12, Medical Service – Major is an allowed use in the PAD.

1. The foundation plan has been reviewed for compliance with DP21-0302 and although the foundation plans match the DP until the DP is approved Zoning cannot approve the foundation plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
03/16/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
03/16/2022 LBOWERS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review