Permit Number: T21CM09774
Parcel: 14101925B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM09774
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2022 JPEELDA1 FIRE REVIEW Approved
01/12/2022 ROBERT SHERRY WATER REVIEW Completed
01/12/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM09774
5755 S Houghton Rd – PAD-12
Medical Service – Major (1st Review) – DP21-0302

TRANSMITTAL: January 12, 2022
This site is located in PAD-12, Medical Service – Major is an allowed use in the PAD.

1. The foundation plan has been reviewed for compliance with DP21-0302 and although the foundation plans match the DP until the DP is approved Zoning cannot approve the foundation plan.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
01/12/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
01/19/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09774


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approval Pending
Approval is for the Foundations only.

BUILDING REVIEW COMMENTS:
Approved
Review for foundation only.

PLUMBING REVIEW COMMENTS:
Approved


PLUMBING REVIEW COMMENTS:
Denied
1). Need to show the Total GPM load for each horizontal Storm Bldg. drain exit terminations on Plan Pages 1P201A,1P201C, 1P201D, 1P201E -IPC 1106.2
2). Provide the civil site utility piping plan to see that it correlates with the foundation plan water, storm, & sewer stub-outs. -IPC A106.3.1
3). The 1/8" pitched 6" Sanitary bldg. drain on 1P201E is undersized. -IPC Table 710.1
4). Washers shown on plan pg. 3AC101 that discharge to the sanitary drainage system on plan Pg. 1P201D need to discharge thru a lint interceptor. -IPC 1003.6
5). Plan Pages 1p201B & 1P201D sectors B&D show a large amount of floor sinks but their use isn't specified or clear. These indirect waste receptors need to comply with IPC 802.1 & 803.1 (the use of the floor sinks in sectors C&E are clear)
6). The 2 sump pumps SP1 #9 will need to discharge to an indirect waste receptor. -IPC 802.1.5, 301.3
7). Natural gas #1 & #2 on 1P301 appear to be piped underground? see IFGC 404.14
8). Is the gas piping in sector E on Plan Pg. 1P301E being routed above grade/slab in it's entirety? IFGC sect 404
9). Provide the proposed gas loads & pressures on plan pages. 1P301c & 1P301E. IFGC 402.3 & 402.7
02/02/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
02/02/2022 VVERA1 OUT TO CUSTOMER Completed