Permit Number: T21CM09674
Parcel: 12809016B

Address:
4701 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM09674
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the location of the proposed indirect waste receptor, FS-1, to ensure that it is visible for inspection and has ready access for cleaning. Reference: Section 802.4, IPC 2018.
2. Revise the vent for the floor sink so that it will rise vertically to at least 6" above the flood rim of the floor sink it protects prior to running horizontally. Reference: Section 905.4, IPC 2018.
01/06/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/06/2022 ROBERT SHERRY WATER REVIEW Completed
01/11/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/13/2022 SSHIELD1 ENGINEERING REVIEW Passed
01/13/2022 STEVE SHIELDS ZONING REVIEW Approved
01/13/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/14/2022 JVINCEN1 FIRE REVIEW Approved
12/29/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved