02/08/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09096


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
Third Review:
1). Same-This occupancy type & load requires a High/Low drinking fountain, can't be substituted. -IPC 403.1 & 410.3
-Tucson Amendment 410.4 Substitution. REVISE section by ADDING a second sentence to read: When a single drinking fountain is required, it may be substituted with a point of use water cooler or dispenser.
-This means if the occupancy load required more drinking fountains than the required 2 as stated in 410.3, the additional drinking fountains could be substituted with water dispensers.
2). OK
3). OK
4). Same -Water Heater detail on plan pg. P3 needs to show a pan & drain. -IPC 504.7
- " code section IPC 504.7 says a water heater pan is required when a water heater is installed in an location where leakage could cause damage"
- this section does not say structural damage & Tucson amendments do not contain a change for this code section as stated in response comments
5). OK
6). OK
03/02/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM09096
1215 E Warehouse Ave – I-1
Medical Service Outpatient (2nd Review)

TRANSMITTAL: March 1, 2022
This site is located in the I-1 zone (UDC 4.7.29). Medical Service Outpatient is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.13.Q.

1. This comment was not addressed, the DP has not been resubmitted with corrections at this time. Zoning has reviewed the building plans for compliance with DP21-0306, although the footprint appears to match what was shown on the DP, Zoning was not able to compare building heights as no proposed height was provided on the DP. Zoning cannot approve the building plans until the DP is approved.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov