Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09096


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approval Pending
1. Door 101A does not swing in the direction of egress. There are more than 50 occupants. Section 1010.1.2.1.


MECHANICAL REVIEW COMMENTS:
Approval Pending
1. Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
1). Same-This occupancy type & load requires a High/Low drinking fountain, can't be substituted. -IPC 403.1 & 410.3
2). Same-Condensate drains on on Plan pg. P1 can't directly connect to the sanitary system ( suggest pipe all to mop sink ,hub drain , or exterior.) -IPC 802.1.5 ( still showing direct connection near lobby on P1)
4). Water Heater detail on plan pg. P3 needs to show a pan & drain. -IPC 504.7
01/21/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM09096
1215 E Warehouse Ave – I-1
Medical Service Outpatient (1st Review)

TRANSMITTAL: January 21, 2022
This site is located in the I-1 zone (UDC 4.7.29). Medical Service Outpatient is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.13.Q.

1. Zoning has reviewed the building plans for compliance with DP21-0306, although the footprint appears to match what was shown on the DP, Zoning was not able to compare building heights as no proposed height was provided on the DP. Zoning cannot approve the building plans until the DP is approved.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov