Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2021 JPEELDA1 FIRE REVIEW Approved
12/06/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM09096

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Please provide a thorough egress plan indicating travel distances and travel paths.
2. Door 130 encroaches into corridor beyond what it permittable. Section 1005.7
3. Door 132 encroaches into corridor beyond what it permittable. Section 1005.7
4. No exit signage is indicated on the RCP plan. Provide exit signage at proper locations.


MECHANICAL REVIEW COMMENTS:
Denied
1. Provide a permanent means of access to equipment located higher than 16'above grade (IMC2018,306.5)
2.Provide mechanical ventilation to enclosed parking garage in an approved manner(needs air supply interlocked with the exhaust) (IMC2018,404)


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
1). This occupancy type & load requires a High/Low drinking fountain, can't be substituted. -IPC 403.1 & 410.3
2). Condensate drains on on Plan pg. P1 can't directly connect to the sanitary system ( suggest pipe all to mop sink , hub drain , or exterior.) -IPC 802.1.5
3). P6 ice maker connection needs ASSE 1022 or 1024 backflow device. update fixture schedule on plan pg P3. -IPC 608.17.1.2
4). Water Heater detail on plan pg. P3 needs to show a pan & drain. -IPC 504.7
5). Site utility piping plan pg. ASP1 and plan pg. P1 need to correlate for the sewer & water BLDG. connection locations. -IPC A106.3.1
6). T5 Restroom Bldg. drain connection on P1 & P2 is illustrated in the wrong direction of flow. -IPC 706.3
12/14/2021 IMONSHI1 ZONING REVIEW Reqs Change FROM: Iman Monshizadeh

PDSD Zoning Review Section

PROJECT: T21CM09096

Plot Plan Review (1st Review)

1215 E Warehouse Av / I-1 Zone

TRANSMITTAL DATE: 12/14/2021



Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.



1.COMMENT: Zoning has reviewed the building plans for compliance with the approved development package. While the building plans are consistent with the approved DP as it relates to the zoning review purview of the Building footprint, Height, square footage, site conditions etc., zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the Development Package.

3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning.



For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp
12/14/2021 ROBERT SHERRY WATER REVIEW Completed
12/14/2021 IMONSHI1 ENGINEERING REVIEW Passed