Permit Number: T21CM08913
Parcel: 141185460

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM08913
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
11/30/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM08913

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

BUILDING REVIEW COMMENTS:
Denied
1. No egress plan provided. Provide a thorough egress plan.
MECHANICAL REVIEW COMMENTS:
Denied
1. Provide exhaust air to the surgical room (IMC2018,403.1)
ELECTRICAL REVIEW COMMENTS
Denied
E1.1: Need to provide exterior lighting energy compliance calculations.
E2: Note 4 calls for 70 amp fuse on a 32KW / 90 amp circuit.
E6: Uprate panel A panel KAIC rating to 22KA to match Panel B.

PLUMBING REVIEW COMMENTS:
Denied
1). This occupancy type and load requires a high/low drinking fountain, can't be substituted. Update plan pages P1, P2, P4 -IPC 403.1 & 410.3
2). High/Low drinking fountain requires a drain. Update plan pages P1, P2,, P4 -IPC 709.1
3). Water Heater requires a Pan update water detail on plan pg. P3 -IPC 504.7
4). Plan pages P1 & P2 water piping illustrations need to show the hot line returning the water heater. -IPC 607.2.1
5). Condensate drains on plan pg. P1 can't directly connect to the sanitary system. ( suggest pipe to mop sink, hub drain or
exterior) -IPC 802.1.5
6). Note #7 on plan pg. P1 states rainwater leaders, but not illustrated? -IPC A106.3.1
7). Plan pages A2.1 thru A4 don't illustrate any type of drainage system? -IPC A106.3.1
11/30/2021 JPEELDA1 FIRE REVIEW Approved
12/06/2021 ROBERT SHERRY WATER REVIEW Completed
12/09/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM08913 – DP21-0236
9517 E Old Vail Rd – I-1
Animal Services (1st Review)

TRANSMITTAL: December 9, 2021
This site is located in the I-1 zone (UDC 4.7.29), Animal Service is an allowed use in the zone (UDC Table 4.8-5) subject to Use Specific Standard 4.9.13.Q.

1. Zoning has reviewed the building plans for compliance with DP21-0236 and although it appears that the plans match Zoning cannot approve the building plans until the DP is approved.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
12/09/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
12/09/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM08913 – DP21-0236
9517 E Old Vail Rd – I-1
Animal Services (1st Review)

TRANSMITTAL: December 9, 2021
This site is located in the I-1 zone (UDC 4.7.29), Animal Service is an allowed use in the zone (UDC Table 4.8-5) subject to Use Specific Standard 4.9.13.Q.

1. Zoning has reviewed the building plans for compliance with DP21-0236 and although it appears that the plans match Zoning cannot approve the building plans until the DP is approved.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/31/2022 VVERA1 OUT TO CUSTOMER Completed