Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM08828
Parcel: 13216061A

Address:
1701 E BENSON HY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM08828
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM08828
1701 E Benson Hw – C-2
Personal Service

TRANSMITTAL: April 4, 2022

Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Personal Storage is an allowed use in the zone (UDC Table 4.8-4) subject to Use Specific Standards 4.9.10.C.3 & .6.

1. This comment was not addressed. Provide a color palate with you next submittal that clearly demonstrates that the requirements of UDC Use Specific Standards 4.9.10.C.3 & .6 are met.

2. Detail 8 sheetSP1.1 does not match the detail on DP21-0044 sheet 3. Either revise the detail on the building plans or the DP. Also the reference to “CLASS II” is incorrect and should be short-term.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
04/06/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM08828


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
NOTE: The response letter says that Sealed and Signed Structural Calculations are submitted with this submittal. NO such calculations were found in this submittal. Submit the following:
1. Provide Structural Calculations for Foundations and Roof Framing per Section 1601.1 of International Building Code 2018.
2. Provide Wind Load Calculations for the Building per Section 1609 of International Building Code 2018.
3. Provide Seismic Calculations for the Building per Section 1613 of International Building Code 2018.
4. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Denied
Mechanical Comment: Comment 1: Provide mechanical plans Response: No mechanical equipment provided at any building – all buildings are non-conditioned spaces.. This is a Storage occupancy and according to the ventilation tables you are still required to ventilate the space. Not Complied


ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Conditionally Approved
Second Review:
1). Complied-City Of Tucson Planning & Development Services approved appeal to not have Plumbing facilities at This Storage Unit Facility. See uploaded Appeal form
2-3 OK


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/12/2022 SBLOOD1 ENGINEERING REVIEW Approved
04/15/2022 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change