Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM08828
Parcel: 13216061A

Address:
1701 E BENSON HY

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM08828
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
11/29/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM08828

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide Structural Calculations for Foundations and Roof Framing per Section 1601.1 of International Building Code 2018.
2. Provide Wind Load Calculations for the Building per Section 1609 of International Building Code 2018.
3. Provide Seismic Calculations for the Building per Section 1613 of International Building Code 2018.
4. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018.
5. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1.
6. Submit documentation regarding implementation of Special Inspections and Testing program during construction to observe compliance with the Design Concepts and Specifications.
7. Provide schedule of special inspections as required in IBC Section 1705.
8. Refer to Drawing S3.3, verify how units with no 4x18Ga Flat straps are stabilize.
9. Structural general notes are to include any components of the building that may be considered deferred submittals. IBC Section 107.3.4.1 requires deferred submittals to be approved by the building official.
If items will be deferred the plans are to clearly note the following per IBC Section 107.3.4.1:
* To be reviewed by design professional in responsible charge.
* Design professional shall affix a notation that the deferred items are in general conformance with their design of the building.
* They shall be submitted for review by the building official.
* Shall not be installed until approved by building official.
10. Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.


BUILDING REVIEW COMMENTS:
Denied
1. The square footages provided on the cover pages do not match the square footages on the development sheets. Please coordinate the correct square footages.


MECHANICAL REVIEW COMMENTS:
Denied
1. Provide mechanical plans (IMC2018,106.3.1)


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
1). Storage facilities do not meet the exception #2 of IPC 403.3 or IBC 2902.3. The customer utilization are is more than 300 square ft & these activities would not be quick transactions. Plumbing Facilities would need to meet the requirements for Occupancy type S1 Load 64. IPC 403.1 ( This could possibly be waved by the BLDG Official)
2). Plans need to include gutter & downspout sizing, with calculations that derive from IPC 1106.2 thru 1106.6 Update plan pg. A3.0 (also include a typical detail of both)
3) Does the facility or dumpster corral have hose faucets? If yes add illustrations & information. IPC A106.3.1
12/01/2021 ROBERT SHERRY WATER REVIEW Passed A water review will be required if plumbing fixtures are added to the plans.
12/02/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM08828
1701 E Benson Hw – C-2
Personal Service

TRANSMITTAL: December 2, 2021
This site is located in the C-2 zone (UDC 4.7.21). Personal Storage is an allowed use in the zone (UDC Table 4.8-4) subject to Use Specific Standards 4.9.10.C.3 & .6.

1. Zoning has reviewed the building plans for compliance with DP21-0044, and although it appears that the plans conform until the DP is approved and the following comments are addressed Zoning cannot approve the building plans.

2. Provide a color palate with you next submittal that clearly demonstrates that the requirements of UDC Use Specific Standards 4.9.10.C.3 & .6 are met.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
12/02/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/29/2021 JPEELDA1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/31/2022 VVERA1 OUT TO CUSTOMER Completed