Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM08617
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM08617
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2021 JPEELDA1 FIRE REVIEW Approved
11/11/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S01; General Notes (Geotechnical Report): Please include a copy of the Geotechnical Report in the next submittal.
2. Sheet S07; Electrical Building: Please provide structural calculations for the Electrical building and foundation design.
3. Sheet S08; Detail 1: Please indicate the footing thickness on this detail.
4. General: Please provide a Special Inspections Certiciate with Parts A and B completed.
5. General: Please provide a project valuation (labor + materials).
6. General: Please provide written responses to all review comments.
11/16/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the building envelope using calculations based on the current code (e.g. provide a COMcheck Envelope Compliance Certificate). Reference: Sections C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2018.
2. Show that the proposed HVAC equipment meets the minimum performance requirements of Section C403.3.2, IECC 2018 (e.g. provide a COMcheck Mechanical Compliance Certificate).
3. Show how one of the "Additional Efficiency Package Options" (C406, IECC 2018) is to be accomplished. Reference: Section C401.2, IECC 2018.
4. Provide smoke detectors in the return air duct, upstream of any outside air connections, for all air distribution systems moving than 2,000 CFM. (This may be in addition to the supply-side smoke detectors shown on the plans.) Reference: Section 606.2.1, IMC 2018, as amended by the City of Tucson.
11/16/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/16/2021 ROBERT SHERRY WATER REVIEW Passed
11/23/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM08617
1102 W Irvington Rd – R-1
TARP Recycled System Source Water Improvements

TRANSMITTAL: November 23, 2021
This site is located in the R-1 zone (UDC 4.7.8). Water distribution System is a permitted use as a Zoning Examiner Special Exception Procedure, Section 3.4.3. in this zone (Table 4.8-2). See Use Specific Standard 4.9.11.A.1, .2, .5, .8, .9, .11.

1. Per UDC Article 3.3.3.G.2.c a Development Plan (DP) is required to be submitted and approved for this project prior to approval of this building plan. The DP shall meet the requirements of the Administrative Manual 2-06. This will also require a Special Exception process per UDC Article 3.4.3 prior to approval of the building permit. Zoning recommends a revision be processed for DP19-0294.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
11/23/2021 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning comments
11/23/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/24/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 . Please indicate what electrical equipment is new and what is existing.

2 . Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting.

3 . Provide compliance with the 2018 IECC for the lighting..

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, 2012 Tucson/Pima County outdoor Lighting Code.