Permit Number: T21CM08136
Parcel: 138211260

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM08136
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM08136

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

Provide a site plan showing all buildings, R106.1.1. Show the location of utility lines to the building.

FLOOR PLAN:

Provide a floor plan showing each room with labeled function and dimensions. Show door locations and window sizes with type identified as XO or SH.

SECTIONS - DETAILS:

New exterior walls require compliant attachment to a 12”x12” reinforced foundation with minimum 6" spacing above exterior grade or 2” above exterior concrete surfaces.

Provide the placement of ceiling/roof insulation. This determines the need for attic ventilation or the need for an air-impermeable layer if insulation at the roof sheathing.

MECHANICAL PLANS:

Provide equipment details showing code compliant components, locations and sizes.

ELECTRICAL PLANS:

Provide wiring details showing code compliant device locations and circuit sizes. Show circuit number and size with receptacles at all walls and lighting control at each doorway both interior and exterior. Receptacle, lighting and smoke detector circuits require arc-fault protection.

INTERNATIONAL ENERGY CONSERVATION CODE:

Provide insulation details minimum (R-13 walls and R-38 ceiling) showing code compliant placement of materials and ratings, N1101. Windows require a solar heat gain of 0.25 or better.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
11/19/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM08136
7240 S Theodore Pl – R-1
Unpermitted Porch Addition (2nd Review)

TRANSMITTAL DATE: November 18, 2021

This site is located in the R-1 zone (UDC 4.7.8). A single family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9.

1. This comment was not addressed. There are 2 structures along the east property line, show them on the plan and include them in the required lot coverage. The plot plan shall show all structures currently on the site along with all applicable perimeter yard setbacks shown.

2. This comment was not addressed. Provide a lot coverage calculation that meets the requirement of UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf, and provide a correct lot coverage calculation.

If you have any questions about this transmittal, please contact Elisa Hamblin at ElisaHamblin@tucsonaz.gov.