Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T21CM08092
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/19/2021 | NMARTEL1 | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL Nicholas Martell, Planner T21CM08092 New SFR October 19, 2021 The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed. 1. Based on the wall height of 9'-6" from model plan T19-M0080, the required side permiter yard setback is 6'-2" to the north property line. The setback of 6', as shown on the plans, does not meet zoning regulations. The applicant may do one of the following: a. Adjust the location of the house to provide the extra two inches. b. Apply for a Design Development Option (DDO) to reduce the required setback. The application can be found here: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf 2. Please remove the walkway from the lot coverage calculation and adjust the percentages accordingly. To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp. If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov |
| 10/29/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 11/04/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Completed |