Permit Number: T21CM07988
Parcel: 10408077E

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM07988
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2021 GSLEIGH1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change Building number required for new detailing building prior to issuance.
10/27/2021 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter serving this new building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
10/28/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM07988 & 7989
4670 N Circuit Rd. – C-3
New Detail Building & Sales Remodel

TRANSMITTAL: October 28, 2021
This site is located in the C-3 zone (UDC 4.7.22), Vehicle Rental and Sales is an allowed use subject to Use Specific Standards 4.9.9.G.1& .2 (Table 4.8-4).

1. Zoning has reviewed the building plan for compliance with DP21-0274 and although it appears that the building plans match the DP Zoning cannot approve the building plans until the DP is approved.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
10/28/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/01/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM07988 & T21CM07989

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. The occupant load factor used for the business area is incorrect. The occupant load factor for business is 150 in accordance with Table 1004.5. Please correct and correlate any applicable requirements.
2. The total occupant load for the detail center is incorrect. The correct factor is present but it was not calculated. Please correct and correlate any applicable requirements.
3. No egress plans are provided. Provided thorough egress plans that show all related egress components and a travels distances from remote points to public way.

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Denied
1. Please provide a prescriptive path or provide COMcheck calculations for the lighting. All mandatory requirements must be identified on the plans for compliance. Reference IECC Section 505.1

PLUMBING REVIEW COMMENTS:
Approved
11/04/2021 IMONSHI1 ENGINEERING REVIEW Passed
11/16/2021 JPEELDA1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/16/2021 VVERA1 OUT TO CUSTOMER Completed