Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T21CM07886
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/12/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL s FROM: PDSD Zoning Review PROJECT: T21CM07886 5250 S Campbell Ave Site #156 Room Addition (1st Review) TRANSMITTAL DATE: October 12, 2021 This site is located in the MH-1 zone (UDC 4.7.10). Mobile Home Park is a permitted use in this zone (Table 4.8-2). 1. As this mobile home is located in a mobile home park and there are not individual parcels for each unit, remove the property lines from the plan and demonstrate that the distance between the proposed addition to adjacent structures meets building code setback requirements. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov |
| 10/21/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 10/27/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Exterior walls with a fire separation distance less than 3-foot to the neighboring property line require not less than one-hour fire-resistive construction. Show compliance with R302.1 (City of Tucson Amended) by providing a section detail of materials prescribed in IBC Table 721.1(2), Items 15-1.1 to 16-1.3. Also, remove window opening from this fire rated wall or provide 3 foot separation from the property line. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Add this layer between the roof sheathing and batt insulation for a total of R-30. |