Permit Number: T21CM07154
Parcel: 10821328B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM07154
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2021 JVINCEN1 FIRE REVIEW Approved
09/14/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/15/2021 ROBERT SHERRY WATER REVIEW Completed
09/15/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/16/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/21/2021 STEVE SHIELDS ZONING REVIEW Approved
09/21/2021 SSHIELD1 ENGINEERING REVIEW Passed
09/21/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/29/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical comments and provide a written response.
1. Provide a complete panel schedule for panel 'A' and show the location on the electrical floor plan.
2. Provide power/disconnect switch for the Water Heater. See plumbing plan for specs.
Ref; 2018 IBC 107.2.1, 2017 NEC, COT Commercial Plan Submittal Requirements.