Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM07154
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/08/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
09/14/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/15/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
09/15/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
09/16/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
09/21/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
09/21/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
09/21/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
09/29/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical comments and provide a written response. 1. Provide a complete panel schedule for panel 'A' and show the location on the electrical floor plan. 2. Provide power/disconnect switch for the Water Heater. See plumbing plan for specs. Ref; 2018 IBC 107.2.1, 2017 NEC, COT Commercial Plan Submittal Requirements. |