The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM06494
Parcel: 13101054A

Address:
4702 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06494
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM06494

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Denied
1 thru 5 OK
6). Now that piping materials were added to plan pg. P001, gas piping is being shown, remove gas piping from the piping
specs or update the plans with gas piping/equipment illustrations & information. IFGC A106.3.1
7). OK
8). Now that storm drainage sizing calculations have been added to plan pg. P304 , please update calculations to derive from
3" of rainfall as per Tucson Plumbing Code Amendments
9). Now that gutter & gutter downspout sizing with calculations have been added to the plan pg. P304 please update
calculations to derive from 3" of rainfall as per Tucson Plumbing Code Amendments. ( plan pg. G3.0 is correct )
10). OK
11/16/2021 ROBERT SHERRY WATER REVIEW Completed
11/29/2021 SBLOOD1 ENGINEERING REVIEW Approved
12/10/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/13/2021 JPEELDA1 FIRE REVIEW Approved
12/13/2021 STEVE SHIELDS ZONING REVIEW Approved