Permit Number: T21CM06468
Parcel: 11014015A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM06468
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2022 LSHAMIS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
08/30/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM06468

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Denied
1. ELECTRICAL ONE-LINE AND SCHEDULES: A short circuit analysis or calculation is required to
justify the 10 KAIC rating for Panel SPLASH is acceptable.


PLUMBING REVIEW COMMENTS:
Denied
1). How will the exterior P7 Drinking fountain drain shown plan pg. 16 be protected from receiving rain water? -IPC 1101.3
2). Locker room P4 trench drain on plan pg. 16 & 17 can't discharge to storm. update PLBG. fixture schedule, PLBG floor
plan, and notes 2&4. -IPC 1104.2
3). Add Rinse shower detail to plan PG. 16 - IPC A106.3.1
4). Add Gas Water Heater detail to plan PG. 16 including intake/Exhaust piping. -IPC A106.3.1
5). Urinals need partitions. update plan Pgs. 10, 16 - IPC 405.3.5
6). Gang showers need valve or valves that have a maximum temperature setting of 120 deg. -See plan pg.17 Plumbing
Specs. the mixing valve at the water heater max setting is 150 deg. and the Symmons shower control is a single pipe
connection type without thermostatic mixing. -IPC 412.4
7). Lavatories need ASSE 1070 mixing valves. update Plumbing specs on plan pg. 17. -IPC 419.5
8). P7A drinking fountain location is not shown on plan pg. 16 plumbing floor plan? -IPC A106.3.1
9). Does the splash pad have potable water connection? if yes show the RPZ backflow protection on the plumbing plans. -
IPC 608.1
10). Third existing urinal shown on Plumbing Demo plan on plan Pg. 15 can not be deleted due to minimum fixture
requirement. update Plumbing floor plan on plan pg.16. and all other affected plan pages, -IPC 403.1
11). Add shower lining material type to be used to plan page 17. --IPC 421.5.2
08/30/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM06468
2900 N Craycroft Rd
Ft Lowell Park – Pool House Renovation, demo of kids pool and add splash pad and shade sail.

TRANSMITTAL: August 30, 2021
COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8).


This site is located in the HRX-2 zone (UDC 4.7.7). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-1). See Use-Specific Standards 4.9.7.6.

1. Exterior work consisting of Pool House Renovation, demo of kids pool and add splash pad and shade sail requires Historic review.

2. A Development Package meeting the minimum requirements of the Checklist for Minor Changes to Commercial/Industrial uses must be submitted and approved prior to approval of this building plan. This checklist can be found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf. This DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, under submission type “Site Review”.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
09/02/2021 ROBERT SHERRY WATER REVIEW Completed
09/02/2021 JVINCEN1 FIRE REVIEW Approved
09/15/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change See zoning comments for need of a DP

Final Status

Task End Date Reviewer's Name Type of Review Description
02/09/2022 VVERA1 OUT TO CUSTOMER Completed