Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM06290
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/14/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments and provide a written response, The panel schedule did not reflect the new Stovetop or Microwave receptacle or loads associated with them. The load calculations are not acceptable as recorded per NEC. See NEC 220.87. Provide total load calculations with the added loads to verify the panel is within its rated capacity. An electrical floorplan was not provided showing the location of panel âKâ and the Stovetop. Provide electrical design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. REF; 2018 IBC 107.2.1, 2017 NEC, |