Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM06290
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/26/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical comment and provide a written response. 1. Provide complete electrical plans including a panel schedule and load calculations for the increased load to the electrical system. Show the location of the panel providing power for the Stovetop and locations. Ref;2018 IBC sec 107.2.1, 2017 NEC 220. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/26/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |