Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM06073
Parcel: 14042021A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06073
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

The comments to the previous electrical plan review is not completely addressed.

Previous comment #1. Where is the proposed location of the ‘Temp Pole’?

Show the dimensions and material of the pole. Verify the pole is structurally strong enough to support the utility drop and electrical equipment mounted to it.

Provide support for the PVC conduit below the panel.

Show the size and conductor type of the grounding electrode conductor.

Indicate the AIC rating of the electrical service equipment. Correlate with TEP Available Fault Current.

Show the electrical information, specifications, and or ratings on the plans.

Provide electrical design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work.

Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements

Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements