| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/23/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments and provide a written response. Provide a site plan showing the location of the proposed Temp Electrical Service Pole and any buildings on the premises. Show the demensions and material of the Pole? Provide support for the PVC conduit below the panel. Show the size and conductor type for the Grounding Electrode Conductor. Indicate the AIC rating of the electrical service equipment. Per TEP supply. An additional permit or a revision to this permit will be required for the wiring of the equipment downstream of the Temporary Service. Justify the reason for the Temp Service and verify that there is an active building permit already on this property. Be advised, electrical service(s) cannot be installed on vacant property without approval by the Chief Building Official. Ref; 2018 IBC sec. 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements. |