Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM06053
Parcel: 11516019R

Address:
1401 W GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06053
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show the hot water recirculation system, including a detail of the system components and the water heater connections. [Third comment: Comment not resolved, see the referenced code sections for guidance. A hot water recirculation system is a viable option. [Second comment: Comment not resolved; a new water heater does not ensure that the water temperature will be maintained for fixtures over 50-feet from the water heater.] [Initial comment: The new developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2018 and C404.5, IECC 2018.]