Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM06053
Parcel: 11516019R

Address:
1401 W GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM06053
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show the hot water recirculation system, including a detail of the system components and the water heater connections. [Third comment: Comment not resolved, see the referenced code sections for guidance. A hot water recirculation system is a viable option. [Second comment: Comment not resolved; a new water heater does not ensure that the water temperature will be maintained for fixtures over 50-feet from the water heater.] [Initial comment: The new developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2018 and C404.5, IECC 2018.]