Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM05532
Parcel: 114512060

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM05532
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Completed
03/02/2022 LBOWERS1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Completed
03/04/2022 STEVE SHIELDS ZONING REVIEW Approved