Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM05449
Parcel: 114512060

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM05449
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2021 DBENOIT1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change PLEASE PROVIDE INDIVIDUAL BULDING NUMBER PRIOR TO PERMIT ISSUANCE.
addressing@pima.gov, 724-9512
07/13/2021 JVINCEN1 FIRE REVIEW Approved
07/22/2021 ROBERT SHERRY WATER REVIEW Completed
07/26/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM05449/5523-5539

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
1. Non-load bearing walls require a deflection track or details to allow for the relative lateral deflection of the
structural members.
2. Refer Drawing S1.2, Deferred Submittals Section references IBC 2012. Provide accurate information regarding
Current Code International Building Code 2018. The information provided is incorrect since State has adopted latest
Codes. Make revisions as needed.

BUILDING REVIEW COMMENTS:
Denied
TYPE A
1. Occupant notification system is required per Section 907.2.9.1 Exception #2 and all applicable requirements of 907.5.
2. No egress plan provided for the Type A building. Provide a full egress plan.
3. No section detail provided for the fire wall. Provide a UL 2 hour listed assembly for the fire wall. The fire wall is required to have a 2 hour fire rated resistance rating per Table 706.4.

TYPE B
1. Occupant notification system is required per Section 907.2.9.1 Exception #2 and all applicable requirements of 907.5.
2. No egress plan provided for the Type B building. Provide a full egress plan.
3. No section detail provided for the fire wall. Provide a UL 2 hour listed assembly for the fire wall. The fire wall is required to have a 2 hour fire rated resistance rating per Table 706.4.

REC BUILDING
1. No egress plan provided for the rec/office building. Provide a full egress plan.

MAINTENANCE BUILDING
1. No construction type provided for the maintenance building. Provide construction type.
2. No occupancy classification provided for the maintenance building. Provide the occupancy classification.
3. No occupancy load provided for the maintenance building. Provide a calculated occupant load.
4. No egress plan provided for the maintenance building. Provide a full egress plan.

MECHANICAL REVIEW COMMENTS:
Denied
1. Provide ceiling radiation dampers on all bathrooms, kitchens on all apartments on this project (IMC2018,607.6.2)
2. Dryer exhaust shall not penetrate fore rated floor/ wall ceiling assembly unless its protected by a shaft for all apartment
units (IMC2018,504.2)
3. Provide conditioned air to exercise room (IMC2018,403.1)
4. Please correct show the Vbz calculation then the Voz calculation (IMC2018,403.1.1,403.3.1.1.1.2,403.3.1.1.1.3)
5. Pool is not under this review per code summary on page 1
ELECTRICAL REVIEW COMMENTS
Denied
E1.0: Architectural comment: Where are units 2, 4, 7, & 8? Seem to have duplicates of 1, 3, 5, & 6. Confirm with Architect.
E1.1: Architectural comment: Are the units properly labeled? Confirm with Architect.
E5.0: No Electrical issues. May want to consider upsizing HP panels to support future EV chargers.

PLUMBING REVIEW COMMENTS:
Approved
07/30/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM05449, T21CM05523, T21CM05524, T21CM05525, T21CM05526, T21CM05527, T21CM05528, T21CM05529, T21CM05530, T21CM05531, T21CM05532, T21CM05533, T21CM05534, T21CM05535, T21CM05536, T21CM05537, T21CM05538 & T21CM05539
2945 N Bear Canyon Rd – R-3
Multi-Family

TRANSMITTAL: July 30, 2021
This site is located in the R-3 zone (UDC Article 4.7.12). A multi-family is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6.

1. Until development package DP21-0174 has been approved Zoning cannot approve the building plans.

2. There appears that there is a discrepancy between the DP and the building plans. DP shows Building Type “B” to have 4 one-bedroom units and 12 two-bedroom units, building plans show 16 two-bedroom units. This will affect the number of required vehicle parking spaces.

3. The development package sheets provided in the building plan set either need to be the stamped approved plans, marked for reference only or removed from the building plan set.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
07/30/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/16/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/16/2021 NGARCIA3 OUT TO CUSTOMER Completed