Permit Number: T21CM05370
Parcel: 11702133A

Address:
1000 N STONE AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM05370
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2021 ELISA HAMBLIN ZONING REVIEW Approved
08/30/2021 SBLOOD1 ENGINEERING REVIEW Approved
08/30/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Specify that the thermostatic mixing valve is listed to ASSE 1070. Verify that the manufacturer of the instantaneous water heater allows the use of a thermostatic mixing valve with the water heater. [Initial comment: Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.]