Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM05370
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/30/2021 | ELISA HAMBLIN | ZONING | REVIEW | Approved | |
| 08/30/2021 | SBLOOD1 | ENGINEERING | REVIEW | Approved | |
| 08/30/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Specify that the thermostatic mixing valve is listed to ASSE 1070. Verify that the manufacturer of the instantaneous water heater allows the use of a thermostatic mixing valve with the water heater. [Initial comment: Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.] |