Permit Number: T21CM05270
Parcel: 140418560

Address:
3350 E MEDINA RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM05270
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2021 IMONSHI1 ZONING REVIEW Reqs Change FROM: Iman Monshizadeh

PDSD Zoning Review Section



PROJECT: T21CM05270 – New Shell Building

Building Plan Review (1st Review) / Relate to [DP21-0111]

3350 E Medina Rd / I-1 Zoning

TRANSMITTAL DATE: 7/2/2021





COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.





1.COMMENT: Zoning cannot approve the building plans until the Development Package has been approved.



2. COMMENT: This site was platted as a condominium plat a block plat. It will be required to consolidate this site into a single parcel prior to approval.



3. COMMENT: Zoning will re review the building plans for consistency to the approved development package on the next submittal, more comments may be forthcoming.





If you have any questions about this transmittal, Contact Iman Monshizadeh by email Iman.Monshizadeh@tucsonaz.gov or contact Elisa Hamblin, at Elisa.Hamblin@tucsonaz.gov
07/20/2021 ROBERT SHERRY WATER REVIEW Completed
07/28/2021 EHAMBLI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
08/06/2021 SBLOOD1 ENGINEERING REVIEW Approved
08/09/2021 JPEELDA1 FIRE REVIEW Reqs Change IFC 2018, 3206.7.5 Number of doors required. The required fire department access doors shall be distributed such that the lineal distance between adjacent fire department access doors does not exceed 125ft measured center to center.

Questions:
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
08/23/2021 PIMA COUNTY 2ND PARTY REVIEW REVIEW Reqs Change T21CM05270 RFC 2nd Party Comments
7/1/2021
ARCHITECTURAL COMMENTS:
1. Add the 2-1/2" steel studs used at the shaft walls to the stud table (allowable ht.)
2. Signage by separate permit, typical.
3. Provide a separate submittal (PDF documents) of Special Inspection Certificates as required by sheet S0.0, including:
Soils, Concrete, Structuralf Welding and high strength bolting, Cold-formed structural steel framing, wood (roof diaphragm), Approved fabricators, Post installed anchors in concrete and masonry. Built-up roofing installation.


PLUMBING COMMENTS:
1. There is a sewer pipe exiting the building shown on the site plan, but there is no plumbing shown below the slab. Is there no sewer below the slab?


MECHANICAL COMMENTS:
No comments.

ELECTRICAL COMMENTS:

1. Provide an Outdoor Lighting Code calculation per Tucson/Pima County OLC ordinance. Weblink:
https://www.tucsonaz.gov/files/pdsd/codes-ordinances/2012_outdoor_lighting_code_.pdf

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2021 VVERA1 OUT TO CUSTOMER Completed