Permit Number: T21CM05141
Parcel: 141148150

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM05141
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2021 JVINCEN1 FIRE REVIEW Approved
07/01/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/06/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC unit. Reference: Section C403.1.1 and C403.3.1, IECC 2018.
2. Provide calculations to verify that adequate ventilation will be provided for the space. Reference: Section 403.3.1.1, IMC 2018.
07/06/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/06/2021 ROBERT SHERRY WATER REVIEW Completed
07/14/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/16/2021 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/19/2021 SBLOOD1 ENGINEERING REVIEW Passed
07/19/2021 STEVE SHIELDS ZONING REVIEW Approved