Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM05141
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/25/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
07/01/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/06/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC unit. Reference: Section C403.1.1 and C403.3.1, IECC 2018. 2. Provide calculations to verify that adequate ventilation will be provided for the space. Reference: Section 403.3.1.1, IMC 2018. |
07/06/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
07/06/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
07/14/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
07/16/2021 | JGARCIA1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
07/19/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
07/19/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved |