Permit Number: T21CM04901
Parcel: 140390420

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T21CM04901
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM04901
5050 E Valencia Rd
New Whataburger (Revision)

TRANSMITTAL: May 5, 2022
This site is located in the C-2 zone (UDC 4.7.22). Food Service is a permitted use in this zone (Table 4.8-4). See Use Specific Standards 4.9.4.M.1 and 4.9.13.P.

1. As there are proposed changes shown to Sheets C1.3 & C5.1 of the development package a revision to the DP must be submitted and approved prior to approval of this revision to the building plan. This DP revision is a separate submittal from the building plan and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submittal Type “Site Review”.

2. The development package sheets provided in the building set, except for sheets C7.1 & C7.2 Utility Plans, need to be the stamped approved development pack sheets, marked for reference only or removed for the building plans. The utility plans need to be reviewed by plumbing.

If you have any questions about this transmittal, please contact Nicholas Ross at Nocholas.Ross@tucsonaz.gov.
05/11/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM04901

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Revision's approved/Subject to field approval

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Denied
First Revised Plan Plumbing Review:
1). Upload original approved plans for comparison to revisions. -IPC A106.3.1
2). Add tea Brewer, soda, & shake machine to back flow preventer schedule on plan page P5.1 -IPC 608.17.1
3). Women's Restroom lavatory & Ice Machine on plan pages P1.2, P3.1 can't discharge to the grease system -IPC 1003.2

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
05/24/2022 JPEELDA1 FIRE REVIEW Approved
06/14/2022 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/14/2022 VVERA1 OUT TO CUSTOMER Completed