Permit Number: T21CM04901
Parcel: 140390420

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM04901
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2021 JPEELDA1 FIRE REVIEW Approved
07/06/2021 ROBERT SHERRY WATER REVIEW Completed
07/07/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM04901

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
Structural steel, components and fasteners for the roof screen are to be protected against corrosion in
accordance with AISC 360 Section B.13 as indicated in IBC 2018 Section 2203.1.
2. Designer is to coordinate venting and drainage hole requirements for HSS tube members that are
galvanized using the hot-dip galvanizing process. Provide for plugs as needed. AWS D-19.0 calls for welds
on galvanized steel to be free of zinc. Field welds on galvanized parts requires the removal of the zinc
coating in the area of weld. Provide zinc paint (approved by the galvanizer) and apply as required to the
weld and steel area to provide protection.
3. Screen wall column locations shown along line 6.6 and the screen wall is shown along line 6.7 on Drawing
S1.2. Coordinate screen wall location with Architectural Drawings.
4. Section D4 on Drawing S3.1 shows combined footing size as 13’x6’. Drawing S1.1 shows combined footing
size as 13’x5’. Investigate and make corrections as needed.
5. Refer Drawing S1.2, Roof Framing Plan. Section A2/A4.2 is called out. Drawing A4.2 is not submitted in
this submittal. Submit Drawing A4.2.
6. Refer Drawing S1.2, Roof Framing Plan. Section A3/A4.2 is called out. Drawing A4.2 is not submitted in
this submittal. Submit Drawing A4.2.
7. Refer Drawing S1.2, Roof Framing Plan. Section A1/A4.3 is called out. Drawing A4.3 is not submitted in
this submittal. Submit Drawing A4.3.
8. Refer Drawing S1.2, Roof Framing Plan. Section A1/A4.4 is called out. Drawing A4.4 is not submitted in
this submittal. Submit Drawing A4.4.
BUILDING REVIEW COMMENTS:
Denied
The occupant load factor for business use is 150 sq ft. per person. This will not affect the occupant load but please
correct.
2. Sheet A1.5 provides documentation for alternative for an alternative acoustical ceiling suspension, however, on sheet
A1.3 a standard seismic bracing detail is provided for a lay in ceiling. Correlate these details and provided an accurate
bracing detail for the proposed acoustical ceiling.

MECHANICAL REVIEW COMMENTS:
Denied
1.provide quantity of CO2 on the premises (imc2018,106.3.1)
2. provide manufacturers kitchen hood specs (imc2018,106.3.1)
3. provide isometric gas pipe plan with gas pressure and pressure drop info (imc2018,106.3.1)
4. provide ventilation table (imc2018,106.3.1)

ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E5.1 ELECTRICAL DIAGRAMS: Should increase size of grounding conductor for ground rod or concrete encasement (Ufer) ground so that it is the primary grounding. Currently the grounding to building steel and water line have the largest grounding conductors
E5.3 CONTROL SYSTEMS PLAN: Should call out all cables that might be installed in duct to be plenum rated.

PLUMBING REVIEW COMMENTS:
Denied
1. Amend sheet G.1 Applicable codes to include the local amendments for the 2018 Plumbing code.
2. Sheet P1.2 must be revised to reflect the requirements of IPC 1003.3 as amended by the local jurisdiction. The following
fixtures are required to be connected to the grease interceptor: All Floor sinks, and Hand sinks
3. Update Sheet P4.1 to reflect the calculation table for the Grease Interceptor as per local amendment
07/13/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM04901
5050 E Valencia Rd
New Whataburger (1st Review)

TRANSMITTAL: June 13, 2021
This site is located in the C-2 zone (UDC 4.7.22). Food Service is a permitted use in this zone (Table 4.8-4). See Use Specific Standards 4.9.4.M.1 and 4.9.13.P.

1. Zoning has reviewed the building plans for compliance with DP21-0172 and although it appears that the building matches what is shown on the DP, until DP21-0172 is approved Zoning cannot approve the building plan.

2. The development package sheets provided in the building plan either need to be the approved stamped sheets, marked for reference only or removed from the building plans.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
07/13/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
07/20/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change Development Package must be approved first.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/20/2021 VVERA1 OUT TO CUSTOMER Completed