Permit Number: T21CM04815
Parcel: 110035860

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM04815
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/08/2021 ROBERT SHERRY WATER REVIEW Completed
09/08/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Second comment: Comment not resolved; ten copies of an incomplete COMcheck Envelope Compliance report is unacceptable.] [Initial comment: The portion of the building shell being modified in this activity does not appear to have been conditioned. Section C503.2, IECC 2018 requires the space to be brought into full compliance with the current energy code. Demonstrate energy code compliance for the building envelope, HVAC, and interior lighting using calculations based on the current code. Reference: Sections C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2018.]
2. Comment not addressed. [Second comment: Coordinate the heating and cooling load calculations with the zoning shown on the mechanical floor plan for HP-5 and HP-6.] [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018.]