Permit Number: T21CM04460
Parcel: 12212115B

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T21CM04460
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Show the location and size of new electric devices and feeders, R106.1.1.

Show service panels on a Riser Diagram for each dwelling. A feeder is required for serving a distribution panel not located with the service meter and disconnect, NEC 225.30 and E3403. Identify existing and new equipment.
11/12/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM04460
1201 N Swan Rd – O-3
Add Second Electrical Service (1st Review)

TRANSMITTAL DATE: November 12, 2021

This site is located in the O-3 zone (UDC 4.7.15), two (2) dwelling units are allowed (UDC Table 4.8-3)

1. Provide approved permit documents that converted the single family dwelling unit into two (2) dwelling units.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
11/12/2021 VVERA1 OUT TO CUSTOMER Completed