Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T21CM04460
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/08/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Show the location and size of new electric devices and feeders, R106.1.1. Show service panels on a Riser Diagram for each dwelling. A feeder is required for serving a distribution panel not located with the service meter and disconnect, NEC 225.30 and E3403. Identify existing and new equipment. |
| 11/12/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM04460 1201 N Swan Rd – O-3 Add Second Electrical Service (1st Review) TRANSMITTAL DATE: November 12, 2021 This site is located in the O-3 zone (UDC 4.7.15), two (2) dwelling units are allowed (UDC Table 4.8-3) 1. Provide approved permit documents that converted the single family dwelling unit into two (2) dwelling units. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/12/2021 | VVERA1 | OUT TO CUSTOMER | Completed |