Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM03940
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/06/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Ref; Plan sheet E1. In the Outdoor Lighting Calculation, the table shows the ‘P’ and ‘F’ luminaires “OPEN TO THE SKY” and also “100% SHEILDED”. Please clarify.. See definitions in the OLC for “Sheilded”. Provide full compliance with the 2018 IECC for the lighting. Do not confuse the IECC with the OLC. Ref; 2018 IBC sec 107.2.1, 2018 IECC, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC). |