Permit Number: T21CM03940
Parcel: 12418053C

Address:
1560 E 17TH ST

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T21CM03940
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/11/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/11/2021 ROBERT SHERRY WATER REVIEW Completed
05/25/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/01/2021 JPEELDA1 FIRE REVIEW Approved Your building is 8,434 IIB construction. We need a letter from Tucson Water stating that the required 2,000 gpm for 2 hours can be achieved. If the 2,000 gpm cannot be met you will need to install fire sprinklers. If you have any questions please contact me.
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
06/01/2021 JPEELDA1 FIRE REVIEW Approved Letter from Tucson Water confirmed that the required fire flow was met. Added the letter to the CM folder and changed to approved.
06/03/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Please update the lighting plans with the following information on the plans;

Provide a complete luminaire schedule. The strip lighting (A) still shows using fluorescent type lighting which is ok, however you may want to upgrade to more efficient LED type.

Revise the Outdoor Lighting Calculations to show the lighting area and correct option. The 55000 lumen cap is used for residential property and LPS type lighting is not applicable, see Table 401.1.

Indicate light source color temperature output and shielding for all exterior luminaires including under canopy .

Provide luminaire manufacture cut sheets with the luminaire specified.

Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

Specify any exceptions used.

Curfew lighting controls If applicable.

Do not confuse the Outdoor Lighting Code with the IECC.

Provide GFI protection for the drinking fountain receptacle. NEC 422.5

Provide a complete grounding detail for the electrical service equipment and building. NEC 250.

Ref; 2018 IBC 107.2.1, 2017 NEC, Tucson/Pima County Outdoor Lighting Code. City of Tucson Commercial Plan Submittal Requirements.
06/07/2021 STEVE SHIELDS ZONING REVIEW Approved
06/16/2021 LOREN MAKUS ENGINEERING REVIEW Approved
07/14/2021 LSHAMIS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/15/2021 VVERA1 OUT TO CUSTOMER Completed