Permit Number: T21CM03789
Parcel: 125074220

Address:
430 N FORGEUS AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM03789
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2021 SBLOOD1 ENGINEERING REVIEW Passed
05/14/2021 AWARNER1 NPPO REVIEW Passed
06/01/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM03789
430 N Forgeus Ave
Master Suite, Guest Suite & Carport Addition

TRANSMITTAL: June 1, 2021
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall, see UDC Article 6.4.5.B & Figure 6.4.5-A.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A).

1. Master suite addition to the south property line, based on a wall height of 9’-6” the required perimeter yard setback is 6’-4”, proposed is 4’-0”.

2. Guest suite addition to the south property line, based on a wall height of 11’-6” the required perimeter yard setback is 11’-4”, proposed is 8’-0”.

3. Guest suite addition to the north property line, based on a wall height of 15’-0” the required perimeter yard setback is 10’-0”, proposed is 6’-0”.

4. Roof deck addition to the south property line, based on a wall height of 17’-0” the required perimeter yard setback is 6’-4”, proposed is 4’-0”.

5. Carport addition to the north property line, based on a wall height of 9’-0” the required perimeter yard setback is 6’-0”, proposed is 3’-0”.




6. The maximum height of a wall or fence within a perimeter yard shall be six (6) feet (UDC Section 6.6.2.I). There is a “SCREEN WALL” called out under Key Note 9 shown on the south elevation that appears to be 8’-0” tall but it is not clear where this is located on the site plan. The only call out on the site plan along the south property line is for a “NEW 6’ STEEL FENCE” under Key note 19. Depending on the location of the screen wall a DDO for wall height maybe required.

DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.
06/03/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM03789

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance.

Place each plan sheet into a single PDF file for reviewing as a complete plan set.