Permit Number: T21CM03689
Parcel: 128061200

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM03689
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM03689
1101 S Van Buren Ave
Residential Care Facility – 10 or less residences (1st Review)

TRANSMITTAL DATE: May 26, 2021

This site is located in the R-1 zone (UDC 4.7.8). Residential Care Services, Adult Care or Physical and Behavioral Health Services is permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.J. 2.a, 3.a, 4

1. As this site is made up of two (2) parcels, 128-06-1190 &128-06-1200 a lot combination is required. Provide a copy of the approved Pima County Assessor’s Combo Request form with your next submittal.


If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov.
06/01/2021 SBLOOD1 ENGINEERING REVIEW Passed
06/01/2021 AWARNER1 NPPO REVIEW Passed
06/02/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/02/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G101; Building and Site Notes: Per the IBC Table 602, Occupancy Classification R that has less than 10' of fire separation (to a property line) must have a fire resistance rating of one hour for exterior walls. Please verify and indicate on the drawings exterior walls meet that criteria as required.
2. Sheet G101: Please provide a Code Analysis for the buildings, including Occupancy Classification, Construction Type, Occupant Load (each structure and total), Plumbing Fixture Requirements, Accessibility Requirements, Allowable Area, Egress Requirements, Type A and B Unit Requirements, and Sprinkler Requirements.
3. Sheet S301 (Roof Framing Plan); Structural Calculations (Sheet 4): The structural calculations indicate Joist J2 at the ramada requires a 4x2x5/16, while the Joist Schedule for the Roof Framing Plan indicates a 4x2x3/16. Please coordinate.
4. Sheet A501; Wall Types: Please indicate on the drawings how the interior walls will be braced to have adequate strength to resist a horizontal load per the IBC Section 1607.15.
5. General: Please provide a Special Inspections Certificate with Parts A and B completed.
6. General: Please provide written responses to all review comments.
06/02/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide structural calculations for the wall supporting the water heater to show that the wall will safely support weight of the water heater and expansion tank. Reference: Section 301.2, IPC 2018.
06/02/2021 ROBERT SHERRY WATER REVIEW Completed
06/02/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the sequence of operation for the exhaust fans providing ventilation for each dwelling. Reference: Section 403.3.2.1, IMC 2018.
2. The Type A and Type B sleeping quarters have a “cantina” with a countertop microwave oven in lieu of a “kitchen” with a range and microwave oven. Show how local exhaust will be provided for the “cantina” per Section 403.3.2.3, IMC 2018.
3. Show how the dryer installations comply with Section 504.6, IMC 2018.
4. Secure the refrigerant circuit access ports of the condensing units to prevent unauthorized access. Reference: Section 1101.10, IMC 2018.
5. The submitted COMcheck Envelope Compliance certificate is based on “Multifamily: Nonresidential”. Revise the energy compliance
06/02/2021 JPEELDA1 FIRE REVIEW Reqs Change 1. Sheet G101: Please provide a Code Analysis for the buildings, including Occupancy Classification, Construction Type, Occupant Load (each structure and total) fire alarm Requirements, and Sprinkler Requirements.
2. General: Please provide written responses to all review comments.

If you have any questions please call or email me:
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033