Permit Number: T21CM03291
Parcel: 14043011A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM03291
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/27/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/27/2021 ROBERT SHERRY WATER REVIEW Passed
04/28/2021 JPEELDA1 FIRE REVIEW Approved
05/04/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide structural calculations for the AVRA Vault Foundation/Wall Plan (Sheets 22 and 23), the Santa Cruz Vault Foundation/Wall Plan (Sheets 24 and 25), and the Control Building (Sheets 26 through 31).
2. General: Please provide a Special Inspections Certificate with Parts A and B complete.
05/11/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response. #1. Ref; Plan Sheet 42 of 58. There is a notation above the bold "SINGLE LINE DIAGRAM" stating "NEW WORK IS SHOWN DARK, EXISTING IS SHOWN LIGHT" . It appears that all is shown in dark. Is this the case? #2. Where is the new electrical service located? #3. Ref; Plan Sheet 37 of 58. Is the control building and associated electrical equipment new? Please clarify.
Ref 2018 IBC 107.2.1, 2017 NEC
05/17/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM03291
990 E Valencia Rd
Water Utility

TRANSMITTAL: May 17, 2021
This site is located in the I-1 zone (UDC 4.7.29). Utility Distribution System is a permitted use subject to Use Specific Standards 4.9.11.B.2, .3, & .5 and 4.9.13.Q.

1. As you are proposing a new building on this site A Development Package (DP) is required that meets the requirements of the checklist for Minor Changes to Commercial/Industrial Sites located at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf, shall be submitted and approved prior to approval of this permit.


If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
05/20/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change See zoning comment for need of DP.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
06/03/2021 LBOWERS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review