Permit Number: T21CM02898
Parcel: 12912100A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM02898
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2021 ROBERT SHERRY WATER REVIEW Reqs Change Show the location and size of the existing water meter, the location of the proposed backflow preventer, and the water service pipe on a site plan. Reference: Section 107.2.6, IBC 2018.
04/14/2021 JPEELDA1 FIRE REVIEW Approved
04/26/2021 LSHAMIS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
04/28/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM02898

GENERAL:
o Provide written responses to all review comments.
o Provide a complete plan set.
o Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
NA
BUILDING REVIEW COMMENTS:
Denied
1. Some the adopted codes listed on the Title Page are incorrect.
2. Provide a thorough code analysis that includes construction type, occupancy type, occupant load calculations, exit
analysis, bathroom requirements, and all other required information.
3. Provide an egress plan that show travel distances, exit sizing and occupant loads.
4. Sheet S1.0: There are several foundation notes that do not apply and list incorrect adopted codes
5. The door schedule provides no information regarding hardware. Provide a hardware schedule and all required
information.
6. Why is the single user bathroom accessible from the outside? Provide additional clarification.
7. Sheet S1.3: What is section H identifying? Show where this section is taking place.
8. Provide wall bracing plan.
9. Provide all structural calculations.
10. Provide all ADA details. No details provided.
ELECTRICAL REVIEW COMMENTS
Approved

MECHANICAL REVIEW COMMENTS:
Denied
1. No comcheck provided.
PLUMBING REVIEW COMMENTS:
Approved
05/03/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM02898
1001 E Silverlake Rd
New Office Building

TRANSMITTAL: May 3, 2021
This site is located in the C-1/C-2 zone (UDC 4.7.20 & 4.7.21). Administrative Office is a permitted use in this zone (Table 4.8-4) subject to Use Specific Standards C-1 4.9.13.O
& C-2 4.9.13.P

1. A development package meeting the requirements of Administrative Manual 2-06 must be submitted and approved prior to approval of the building plans.

If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov.
05/03/2021 SSHIELD1 ENGINEERING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM02898
1001 E Silverlake Rd
New Office Building

TRANSMITTAL: May 3, 2021
This site is located in the C-1/C-2 zone (UDC 4.7.20 & 4.7.21). Administrative Office is a permitted use in this zone (Table 4.8-4) subject to Use Specific Standards C-1 4.9.13.O
& C-2 4.9.13.P

1. A development package meeting the requirements of Administrative Manual 2-06 must be submitted and approved prior to approval of the building plans.

If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov.