Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM02898
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/13/2021 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Show the location and size of the existing water meter, the location of the proposed backflow preventer, and the water service pipe on a site plan. Reference: Section 107.2.6, IBC 2018. |
| 04/14/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 04/26/2021 | LSHAMIS1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 04/28/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM02898 GENERAL: o Provide written responses to all review comments. o Provide a complete plan set. o Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: NA BUILDING REVIEW COMMENTS: Denied 1. Some the adopted codes listed on the Title Page are incorrect. 2. Provide a thorough code analysis that includes construction type, occupancy type, occupant load calculations, exit analysis, bathroom requirements, and all other required information. 3. Provide an egress plan that show travel distances, exit sizing and occupant loads. 4. Sheet S1.0: There are several foundation notes that do not apply and list incorrect adopted codes 5. The door schedule provides no information regarding hardware. Provide a hardware schedule and all required information. 6. Why is the single user bathroom accessible from the outside? Provide additional clarification. 7. Sheet S1.3: What is section H identifying? Show where this section is taking place. 8. Provide wall bracing plan. 9. Provide all structural calculations. 10. Provide all ADA details. No details provided. ELECTRICAL REVIEW COMMENTS Approved MECHANICAL REVIEW COMMENTS: Denied 1. No comcheck provided. PLUMBING REVIEW COMMENTS: Approved |
| 05/03/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM02898 1001 E Silverlake Rd New Office Building TRANSMITTAL: May 3, 2021 This site is located in the C-1/C-2 zone (UDC 4.7.20 & 4.7.21). Administrative Office is a permitted use in this zone (Table 4.8-4) subject to Use Specific Standards C-1 4.9.13.O & C-2 4.9.13.P 1. A development package meeting the requirements of Administrative Manual 2-06 must be submitted and approved prior to approval of the building plans. If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov. |
| 05/03/2021 | SSHIELD1 | ENGINEERING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM02898 1001 E Silverlake Rd New Office Building TRANSMITTAL: May 3, 2021 This site is located in the C-1/C-2 zone (UDC 4.7.20 & 4.7.21). Administrative Office is a permitted use in this zone (Table 4.8-4) subject to Use Specific Standards C-1 4.9.13.O & C-2 4.9.13.P 1. A development package meeting the requirements of Administrative Manual 2-06 must be submitted and approved prior to approval of the building plans. If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov. |